Fire Alarm System Requirements

q       One complete set of construction documents:

o       Signed and Sealed

o       Properly scaled

o       On same size pages

o       Legible

o       Showing fire alarm components only

o       All rooms identified

o       All fire rated walls, floors and ceilings identified

 

q       Construction documents shall show:

o       Symbols confirming to NFPA 170 or symbol key for non-standard symbols

o       Location of devices and appliances

o       Height of all pull stations and horn or horn strobe components

o       End of line devices

o       Conduit wire runs

o       Conduit size

o       Number and size of conductors

o       Zone indication shall be placed adjacent to the appropriate end of line device

o       Full point to point or typical point to point wiring configuration

o       All initiating and notification circuits shall be identified

o       Any auxiliary functions

o       Total number of all alarm initiating devices and alarm indicating appliances

o       Sequence of operation matrix

 

q       Manufacturers catalog cut sheets for all devices and appliances

o       All equipment be listed for commercial use

 

q       Documentation on sealing of all penetrations

o       Fire rating of walls, floors and ceilings are__________________

o       Materials used meet ASTM E814 or E119

o       Details on method to be used to provide fire rating of penetration

o       Fire-stop systems or devices listed by UL or independent testing lab 

o       Approved methods attached to construction documents

 

q       Battery calculations

o       Voltage drop calculations

o       Circuit amperage

o       Include standby and alarm conditions calculations

 

q       Central Station Information-must be listed by UL or FM

o       Name of Company  _________________________________________

o       Address  __________________________________________________

o       Business Phone Number______________________________________

o       Contact person _____________________________________________

o       Method of transmission ______________________________________

o       Phone number to our dispatch center ____________________________

 

The following will be checked at the time of the acceptance test

 

q       Will sound pressure levels for audible indication devices meet the requirements of NFPA 72 and the International Building Code?

q       Will visible appliances meet the requirements of NFPA 72, International Building Code and the ADA guidelines?

q       Fire alarm control panel(s) and remote annunciator(s) shall visibly display the location of the alarm in alpha-numeric text

o       The location of the alarm must be specific

o       Provide enough information to determine source of alarm